Air Cooled Heat Exchanger Design Formula
The basic air cooled heat exchanger design formula is based on the heat transfer equation:
Q = U × A × F × ΔTlm
This equation determines how much heat can be transferred between the process fluid and the cooling air through the exchanger surface.
| Symbol | Meaning | Typical Unit |
|---|---|---|
| Q | Heat duty or heat transfer rate | W or kW |
| U | Overall heat transfer coefficient | W/m²·K |
| A | Effective heat transfer area | m² |
| F | LMTD correction factor | Dimensionless |
| ΔTlm | Log mean temperature difference | K or °C |
For preliminary ACHE sizing, the required heat transfer area can be calculated by rearranging the equation:
A = Q / (U × F × ΔTlm)
Before calculating the surface area, the required heat duty is usually determined from the process-fluid energy balance:
Q = ṁ × Cp × (Tin − Tout)
where (ṁ) is the process-fluid mass flow rate, (Cp) is the specific heat capacity, and (Tin) and (Tout) are the fluid inlet and outlet temperatures.
The temperature driving force is commonly expressed using the log mean temperature difference:
ΔTlm = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2)
For example, if the exchanger duty is 500 kW, the overall heat transfer coefficient is 50 W/m²·K, the uncorrected LMTD is 40 K, and the LMTD correction factor is 0.9 , the required heat transfer area is:
A = 500,000 / (50 × 40 × 0.9) = 277.8 m²
This calculated area provides a preliminary basis for selecting the finned-tube bundle. Final air cooled heat exchanger design must also account for fin efficiency, tube geometry, airflow, tube-side and air-side pressure drop, fouling, and fan performance.
Data Required for ACHE Design
Before starting an air cooled heat exchanger design calculation, the required input data should be collected for the process fluid, ambient air, pressure limits, and exchanger geometry. These inputs determine the heat duty, airflow requirement, heat transfer area, pressure drop, and final tube-bundle configuration.
| Input Category | Required Data | Why It Is Needed |
|---|---|---|
| Process conditions | Fluid flow rate, inlet temperature, outlet temperature | Used to calculate heat duty |
| Fluid properties | Specific heat, density, viscosity, thermal conductivity | Required for heat transfer and pressure-drop calculations |
| Pressure data | Operating pressure, design pressure, allowable pressure drop | Used for hydraulic and mechanical design |
| Ambient conditions | Design air temperature, site elevation, humidity where relevant | Affects air density, airflow, and thermal performance |
| Tube data | Tube OD, wall thickness, tube length, tube material | Used to calculate flow area and heat transfer surface |
| Fin data | Fin height, thickness, spacing, density, and material | Determines effective surface area and air-side performance |
| Design allowances | Fouling factor, corrosion allowance, design margin | Provides allowance for operating degradation and uncertainty |
| Configuration | Forced or induced draft, tube rows, tube passes | Influences airflow, pressure drop, and exchanger layout |
For preliminary ACHE sizing, the minimum process data normally includes mass flow rate, fluid inlet and outlet temperatures, fluid properties, design ambient air temperature, and allowable pressure drop.
Some parameters are fixed by the process requirements, while others are selected during thermal design. Flow rate, operating temperature, pressure, fluid composition, and required outlet temperature usually come from the process design basis. Tube diameter, tube length, fin geometry, number of rows, number of passes, and fan arrangement are generally optimized during the exchanger sizing process.
The ambient design temperature is especially important because an air cooled heat exchanger depends directly on atmospheric air as the cooling medium. Site elevation should also be considered because lower air density at higher elevations can increase the required volumetric airflow.
For condensing, vaporizing, or multicomponent services, additional data such as fluid composition, phase properties, latent heat, vapor fraction, and temperature-dependent physical properties may be required.
Accurate input data is essential because errors in flow rate, fluid properties, ambient temperature, or allowable pressure drop can significantly affect the calculated heat transfer area, airflow requirement, tube count, and fan power.
Step-by-Step Air Cooled Heat Exchanger Design Calculation
An air cooled heat exchanger (ACHE) is sized by first determining the required heat duty and then calculating the airflow, temperature driving force, heat transfer coefficient, surface area, tube arrangement, and pressure drop. Because several design variables depend on one another, the calculation is usually iterative: an initial geometry is selected, its thermal and hydraulic performance is checked, and the design is adjusted until the required duty and pressure-drop limits are satisfied.
Step 1: Calculate the Required Heat Duty
For single-phase cooling, the process-side heat duty can be calculated from:
Q = ṁ × Cp × (Tin − Tout)
where:
- Q = heat duty, W
- ṁ = process-fluid mass flow rate, kg/s
- Cp = specific heat capacity, J/kg·K
- Tin = process inlet temperature, °C
- Tout = required process outlet temperature, °C
For example, if a process fluid flows at 10 kg/s, has a specific heat of 2,500 J/kg·K, and must be cooled from 120°C to 80°C:
Q = 10 × 2500 × (120 − 80)
Q = 1,000,000 W = 1,000 kW
The ACHE must therefore remove approximately 1,000 kW of heat.
For condensing or two-phase service, latent heat and phase-change enthalpy must also be included.
Step 2: Establish the Design Ambient Air Temperature
The inlet cooling-air temperature should represent the site's design ambient condition rather than a convenient annual-average temperature.
Assume:
Tair,in = 35°C
The expected air outlet temperature must also be estimated. If an initial air temperature rise of 15°C is selected:
Tair,out = 50°C
The selected ambient condition strongly affects exchanger size. A higher inlet-air temperature reduces the available temperature driving force and generally increases the required heat transfer area.
Site elevation should also be considered because air density decreases with altitude, increasing the volumetric airflow required for the same mass flow.
Step 3: Calculate the Required Cooling-Air Flow Rate
Apply an energy balance to the air side:
Q = ṁair × Cp,air × (Tair,out − Tair,in)
Therefore:
ṁair = Q / [Cp,air × (Tair,out − Tair,in)]
Using:
- Q = 1,000,000 W
- Cp,air = 1005 J/kg·K
- Tair,in = 35°C
- Tair,out = 50°C
ṁair = 1,000,000 / (1005 × 15)
ṁair ≈ 66.3 kg/s
If the air density at the design condition is approximately 1.1 kg/m³:
V̇air = 66.3 / 1.1 ≈ 60.3 m³/s
The required airflow is therefore approximately 60 m³/s before allowing for design margin or fan-performance corrections.
Step 4: Calculate the Log Mean Temperature Difference
The temperature driving force between the hot process fluid and cooling air changes across the exchanger. A log mean temperature difference can be used for preliminary thermal sizing.
The two terminal temperature differences are:
ΔT1 = Thot,in − Tair,out
ΔT2 = Thot,out − Tair,in
Using the example:
ΔT1 = 120 − 50 = 70°C
ΔT2 = 80 − 35 = 45°C
Then:
ΔTlm = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2)
ΔTlm = (70 − 45) / ln(70 / 45) ≈ 56.6°C
Because an ACHE normally involves crossflow rather than ideal countercurrent flow, the temperature driving force should be corrected using an appropriate configuration-dependent correction method. The assumed value F=0.90 below is used only to illustrate the preliminary calculation and should not be treated as a universal design value.
If:
F = 0.90
then the corrected temperature driving force is:
F × ΔTlm = 0.90 × 56.6 = 50.9°C
Step 5: Estimate the Overall Heat Transfer Coefficient
For preliminary sizing, an initial overall heat transfer coefficient (U) is assumed based on the process fluid, finned-tube geometry, airflow, fouling condition, and previous design experience.
Assume initially:
U = 50 W/m²·K
The overall coefficient represents the combined resistance to heat transfer through:
- the process-side fluid film,
- the tube wall,
- fouling layers,
- the external air film,
- and the finned surface.
A more detailed design later recalculates (U) from the individual resistances instead of relying only on the assumed value.
Step 6: Calculate the Required Heat Transfer Area
The basic thermal design equation is:
Q = U × A × F × ΔTlm
Therefore:
A = Q / (U × F × ΔTlm)
Using the example:
A = 1,000,000 / (50 × 0.90 × 56.6)
A ≈ 392.6 m²
The preliminary required heat transfer area is therefore approximately 393 m².
A design margin may be added depending on the service, fouling tendency, uncertainty in heat transfer coefficients, and project requirements.
Step 7: Select the Finned-Tube Geometry
The next step is to select a practical finned-tube configuration that can provide the required surface area.
Typical design variables include:
- tube outside diameter,
- tube wall thickness,
- tube length,
- fin outside diameter,
- fin height,
- fin thickness,
- fin pitch or fins per unit length,
- tube material,
- fin material,
- transverse tube pitch,
- longitudinal tube pitch.
Finned tubes are used because the air-side heat transfer coefficient is relatively low. The fins provide a much larger external area, reducing the amount of bare tube surface required.
The selected geometry must balance heat transfer performance against air-side pressure drop and fan power.
Step 8: Calculate the Number of Tubes
Once the effective surface area provided by one finned tube is known, the required tube count can be estimated from:
Nt = Arequired / Aeffective,tube
If one selected finned tube provides an effective external area of 3.5 m²:
Nt = 392.6 / 3.5
Nt ≈ 112
The preliminary design would therefore require approximately 112 finned tubes.
In practice, the number may be rounded upward to suit the selected number of tube rows, passes, bundle width, and fabrication layout.
Step 9: Select Tube Rows and Passes
The total tube count must be arranged into a practical bundle.
For example, 112 tubes may be arranged as:
- 4 tube rows,
- 28 tubes per row,
- 2 tube-side passes.
The number of rows affects air-side heat transfer and pressure drop, while the number of passes affects tube-side velocity and hydraulic resistance.
Increasing the number of passes usually increases process-fluid velocity and heat transfer coefficient, but it also increases pressure drop.
Step 10: Calculate Tube-Side Velocity
Tube-side velocity should be checked after the tube count and pass arrangement are selected.
The flow area per pass is:
Aflow = Ntubes,pass × (π × Di² / 4)
The average process-fluid velocity is then:
V = ṁ / (ρ × Aflow)
where:
- V = tube-side velocity, m/s
- ρ = process-fluid density, kg/m³
- Di = tube inside diameter, m
The calculated velocity should provide adequate heat transfer while remaining within allowable erosion and pressure-drop limits.
If the velocity is too low, fewer tubes per pass or additional passes may be needed. If the velocity is too high, the tube count or flow area may need to increase.
Step 11: Calculate the Tube-Side Heat Transfer Coefficient
The tube-side heat transfer coefficient is normally calculated using suitable forced-convection correlations.
First calculate the Reynolds number:
Re = (ρ × V × Di) / μ
Then calculate the Prandtl number:
Pr = (Cp × μ) / k
where:
- μ = dynamic viscosity
- k = fluid thermal conductivity
A suitable Nusselt-number correlation can then be applied depending on whether the flow is laminar, transitional, or turbulent.
The heat transfer coefficient is obtained from:
hi = (Nu × k) / Di
The correct correlation should match the actual flow regime, tube geometry, property variation, and service conditions.
Step 12: Calculate the Air-Side Heat Transfer Performance
The external air-side coefficient depends strongly on:
- air velocity,
- fin geometry,
- tube pitch,
- number of tube rows,
- air properties,
- bundle arrangement.
Because fins increase the external surface area, fin efficiency must also be considered.
The effective external area can be represented by:
Aeff = Abare + ηf × Af
where:
- Abare = exposed bare-tube area,
- Af = fin area,
- ηf = fin efficiency.
The air-side resistance is often one of the dominant thermal resistances in an air cooled exchanger, so accurate treatment of fin efficiency and airflow is important.
Step 13: Recalculate the Overall Heat Transfer Coefficient
After calculating the tube-side and air-side coefficients, the assumed U-value should be checked.
Conceptually, the overall resistance contains:
1 / U = Rtube-side + Rfouling + Rwall + Rair-side
The exact expression depends on the surface-area basis used.
If the recalculated U-value differs significantly from the initial assumed value of 50 W/m²·K, the required heat transfer area must be recalculated.
For example, if the actual calculated value is only:
U = 42 W/m²·K
then:
A = 1,000,000 / (42 × 0.90 × 56.6) ≈ 467.6 m²
The original 393 m² surface would no longer be sufficient, so additional tubes or a different fin geometry would be required.
Step 14: Calculate Tube-Side Pressure Drop
The process-side pressure drop must be checked against the allowable limit.
The calculation normally includes:
- friction through straight tube lengths,
- inlet and exit losses,
- return losses between passes,
- header losses,
- nozzle losses where applicable.
The result must satisfy:
ΔPcalculated ≤ ΔPallowable
If the calculated pressure drop is too high, possible adjustments include increasing tube diameter, increasing the number of tubes, reducing the number of passes, or changing the bundle geometry.
Step 15: Calculate Air-Side Pressure Drop and Check the Final Design
Air flowing through the finned-tube bundle also experiences resistance. Air-side pressure drop is affected by:
- face velocity,
- fin density,
- tube pitch,
- fin dimensions,
- number of rows,
- bundle arrangement.
The fan must provide sufficient static pressure to overcome the bundle and system resistance while delivering the required airflow.
The final design should satisfy three basic checks:
Qactual ≥ Qrequired
ΔPtube ≤ ΔPallowable
V̇air,fan ≥ V̇air,required
If any of these conditions is not met, the tube count, fin geometry, rows, passes, airflow, or fan selection must be revised and the calculation repeated.
The practical ACHE design sequence is therefore:
Heat duty → airflow → LMTD → initial U-value → required area → finned-tube selection → tube count → rows and passes → heat transfer coefficients → revised U-value → pressure-drop checks → fan requirement → design iteration.
A preliminary manual calculation can establish a reasonable exchanger size, but detailed thermal rating normally requires accurate fluid properties, finned-tube correlations, fan-performance data, mechanical constraints, and service-specific design requirements.
Air-Side Design Calculation
The air-side design calculation determines the airflow, face velocity, heat-transfer performance, fin efficiency, and pressure drop across the ACHE tube bundle. The required air mass flow rate is obtained from the heat balance:
ṁair = Q / [Cp,air × (Tair,out − Tair,in)]
Volumetric airflow is then:
V̇air = ṁair / ρair
where (ρair) should correspond to the design ambient temperature and site elevation.
The bundle face velocity is calculated from:
Vf = V̇air / Aface
Face velocity influences both the air-side heat transfer coefficient and pressure drop. Higher velocity generally improves heat transfer but increases fan power requirements.
Because ACHEs use finned tubes, the effective external surface area should account for fin efficiency:
Aeff = Abare + ηf × Afin
The air-side heat transfer coefficient depends on Reynolds number, fin geometry, tube pitch, airflow velocity, and tube-row arrangement.
Finally, calculate the air-side pressure drop through the finned-tube bundle and verify that the selected fan can provide the required airflow at the calculated static pressure.
ΔPair ≤ ΔPfan,available
Air Cooled Heat Exchanger Fan Sizing
Fan sizing for an air cooled heat exchanger depends mainly on the required airflow and the total air-side pressure drop through the exchanger system. The required volumetric airflow is calculated from the air mass flow rate:
V̇air = ṁair / ρair
where (ṁair) is the required air mass flow rate and (ρair) is the air density at the design ambient condition.
The fan must also overcome the total system resistance:
ΔPtotal = ΔPbundle + ΔPlouvers + ΔPguards + ΔPother
Fan shaft power can then be estimated from:
Pfan = (V̇air × ΔPtotal) / ηfan
where (ηfan) is the fan efficiency.
The number of fans, fan diameter, blade pitch, and operating speed are selected to deliver the required airflow at the calculated static pressure. A suitable margin should also be considered when selecting motor power.
Final fan selection should be checked against the manufacturer’s fan performance curve to confirm that:
V̇fan ≥ V̇required
and
ΔPfan ≥ ΔPsystem
This ensures adequate cooling-air flow under the specified design conditions.
Complete ACHE Design Calculation Example
Consider an air cooled heat exchanger designed to cool a process fluid from 120°C to 80°C at a flow rate of 10 kg/s. Assume (C\_p = 2.5\ kJ/kg·K), ambient air enters at 35°C, air leaves at 50°C, and the preliminary overall heat transfer coefficient is 50 W/m²·K.
1. Heat Duty
Q = ṁ × Cp × (Tin − Tout)
Q = 10 × 2500 × (120 − 80) = 1,000,000 W
So, the required heat duty is 1,000 kW.
2. Required Airflow
ṁair = Q / [Cp,air × (Tair,out − Tair,in)]
Using (Cp,air = 1005 J/kg·K):
ṁair = 1,000,000 / (1005 × 15) = 66.3 kg/s
At an air density of 1.1 kg/m³:
V̇air = 60.3 m³/s
3. LMTD
ΔT1 = 120 − 50 = 70°C
ΔT2 = 80 − 35 = 45°C
ΔTlm = (70 − 45) / ln(70 / 45) = 56.6°C
Assuming (F=0.90), the corrected temperature difference is 50.9°C.
4. Required Heat Transfer Area
A = Q / (U × F × ΔTlm)
A = 1,000,000 / (50 × 0.90 × 56.6) = 392.6 m²
If each finned tube provides 3.5 m² of effective area:
Nt = 392.6 / 3.5 ≈ 112
A preliminary configuration could therefore use 112 finned tubes arranged in 4 rows with 2 passes.
| Parameter | Result |
|---|---|
| Heat duty | 1,000 kW |
| Airflow | 60.3 m³/s |
| LMTD | 56.6°C |
| Required area | 392.6 m² |
| Tube count | 112 |
The final design must still verify tube-side and air-side pressure drop, actual U-value, fin performance, and fan power.
Final ACHE Design Results
The preliminary ACHE design is finalized after confirming that the required thermal duty, heat transfer area, airflow, and pressure-drop limits are satisfied. Based on the worked calculation, the main design results are summarized below.
| Design Parameter | Final Result |
|---|---|
| Heat duty | 1,000 kW |
| Process inlet temperature | 120°C |
| Process outlet temperature | 80°C |
| Design ambient temperature | 35°C |
| Air outlet temperature | 50°C |
| Required airflow | 60.3 m³/s |
| LMTD | 56.6°C |
| Corrected temperature difference | 50.9°C |
| Overall heat transfer coefficient | 50 W/m²·K |
| Required heat transfer area | 392.6 m² |
| Number of finned tubes | 112 |
| Tube rows | 4 |
| Tube passes | 2 |
The final design should satisfy the following checks:
Qactual ≥ Qrequired
Aactual ≥ Arequired
ΔPtube ≤ ΔPallowable
V̇fan ≥ V̇required
If these thermal, hydraulic, and airflow conditions are met, the selected tube bundle and fan arrangement can be considered suitable for preliminary ACHE design. Detailed design should then verify actual U-value, fin performance, pressure drops, fan static pressure, motor power, and applicable project or API 661 requirements.
API 661 Design Considerations
API 661 provides requirements and recommendations for air cooled heat exchangers used mainly in petroleum, petrochemical, and natural-gas services. After completing the thermal design calculation, the exchanger should also be checked for mechanical, air-side, material, testing, and documentation requirements.
| Design Area | Key Consideration |
|---|---|
| Tube bundle | Tube layout, finned tubes, rows, passes, and bundle arrangement |
| Headers | Pressure design, accessibility, connections, and maintenance |
| Fans | Fan arrangement, airflow capacity, operating speed, and controls |
| Air side | Air distribution, louvers, recirculation, and bundle pressure drop |
| Materials | Suitability of tubes, fins, headers, and structural components |
| Structure | Supports, vibration, mechanical integrity, and accessibility |
| Testing | Pressure testing, inspection, quality control, and shop checks |
| Documentation | Datasheets, design conditions, materials, and purchaser requirements |
API 661 compliance involves more than meeting the required heat duty. The final ACHE should also satisfy applicable pressure, mechanical reliability, airflow, inspection, testing, and maintainability requirements.
For detailed design, the applicable edition of API 661, project specifications, and purchaser requirements should be reviewed because these may define additional mandatory design criteria.
Common ACHE Design Calculation Mistakes
Errors in air cooled heat exchanger design can lead to insufficient cooling, excessive pressure drop, unnecessary surface area, or high fan power. The most common mistakes usually involve incorrect assumptions, incomplete air-side calculations, and failure to iterate the design.
| Common Mistake | Why It Matters | Correct Approach |
|---|---|---|
| Using average ambient temperature | Can undersize the ACHE during hot weather | Use the site design ambient temperature |
| Incorrect LMTD or correction factor | Produces the wrong heat transfer area | Verify terminal temperatures and crossflow correction |
| Assuming U-value without checking | May overestimate thermal performance | Recalculate the overall heat transfer coefficient |
| Ignoring fin efficiency | Overstates effective finned area | Include fin efficiency in the area calculation |
| Ignoring site elevation | Underestimates required volumetric airflow | Correct air density for altitude |
| Excessive fin density | Increases air-side pressure drop and fan power | Optimize fin spacing and surface area |
| Ignoring pressure drop | Can make the design hydraulically unacceptable | Check both tube-side and air-side pressure drop |
| Skipping design iteration | Geometry may not meet actual duty | Recalculate until thermal and hydraulic requirements converge |
Before finalizing the ACHE, verify heat duty, U-value, heat transfer area, airflow, tube velocity, pressure drops, and fan capacity together rather than checking each parameter independently.
Manual Calculation vs Design Software
Manual calculations are useful for preliminary ACHE sizing, quick feasibility checks, and verifying whether a proposed design is reasonable. Basic calculations such as heat duty, LMTD, required heat transfer area, airflow, and approximate pressure drop can be performed manually or in Excel.
| Design Aspect | Manual Calculation | Design Software |
|---|---|---|
| Heat duty | Suitable | Suitable |
| LMTD and area | Suitable | Suitable |
| Fluid properties | Simplified | Detailed |
| Fin performance | Approximate | More detailed |
| Pressure drop | Approximate | More detailed |
| Two-phase service | Difficult | Better suited |
| Design iteration | Time-consuming | Faster |
| Optimization | Limited | Strong |
Specialized software such as HTRI or Aspen EDR is generally more suitable for detailed thermal rating because it can handle complex fluid properties, finned-tube correlations, pressure-drop calculations, multiple design iterations, and different operating cases.
A practical approach is to use manual calculations for preliminary sizing and independent checks, then use validated design software or vendor calculations for detailed ACHE design and final performance verification.
Air Cooled Heat Exchanger Design FAQs
1.How do you calculate an air cooled heat exchanger?
ACHE design begins with the required heat duty, followed by calculation of airflow, LMTD, overall heat transfer coefficient, and required surface area. The preliminary heat transfer area is calculated using:
A = Q / (U × F × ΔTlm)
The design is then checked for tube configuration, pressure drop, fin performance, and fan capacity.
2. What is the basic ACHE design formula?
The main thermal design equation is:
Q = U × A × F × ΔTlm
where (Q) is heat duty, (U) is the overall heat transfer coefficient, (A) is heat transfer area, (F) is the correction factor, and (ΔTlm) is the log mean temperature difference.
3. How do you calculate heat transfer area for an ACHE?
The required heat transfer area is calculated from:
A = Q / (U × F × ΔTlm)
Higher heat duty requires more surface area, while a higher overall heat transfer coefficient or larger temperature driving force reduces the required area.
4. How do you calculate airflow for an air cooled heat exchanger?
Required air mass flow is obtained from the air-side energy balance:
ṁair = Q / [Cp,air × (Tair,out − Tair,in)]
Volumetric airflow is then calculated using:
V̇air = ṁair / ρair
Air density should reflect the design ambient temperature and site elevation.
5. How is pressure drop calculated in an ACHE?
Pressure drop must be checked on both the process and air sides. Tube-side pressure drop includes friction, return, header, and nozzle losses, while air-side pressure drop depends on face velocity, fin density, tube pitch, and number of tube rows. Both values must remain within allowable design limits.
6. How do you size an ACHE fan?
Fan sizing is based on required volumetric airflow and total air-side system resistance. Approximate fan power can be calculated from:
Pfan = (V̇air × ΔP) / ηfan
The selected fan should deliver the required airflow at the calculated static pressure and be verified against its performance curve.
7. Why are finned tubes used in air cooled heat exchangers?
Air has a relatively low heat transfer coefficient compared with most process fluids. Fins increase the external surface area available for heat transfer, improving air-side performance without requiring a proportionally larger tube bundle. Fin efficiency and air-side pressure drop must still be considered in the design.
8. How does ambient temperature affect ACHE sizing?
Higher ambient air temperature reduces the temperature difference between the process fluid and cooling air. This lowers the thermal driving force and can increase the required heat transfer area or airflow. For this reason, ACHE design should use an appropriate site design ambient temperature rather than an annual average value.
9. What is API 661 in air cooled heat exchanger design?
API 661 is a widely used standard for air cooled heat exchangers in petroleum, petrochemical, and natural-gas services. It addresses design, materials, fabrication, inspection, testing, and related requirements. Project specifications and the applicable edition of the standard should be reviewed during detailed design.
10. Can an ACHE be designed manually?
Manual calculations or Excel spreadsheets are useful for preliminary sizing, feasibility studies, and independent checks. Detailed thermal design normally requires more accurate fluid properties, finned-tube correlations, pressure-drop methods, fan data, and iterative calculations. Specialized software or validated vendor calculations are therefore commonly used for final performance verification.